商业参考建筑室内空气质量分析

Indoor Air Quality Analysis of Commercial Reference Buildings

 

作者:Ng, L.Musser, A.Persily, A. K.Emmerich, S. 作者单位:National Inst. of Standards and Technology (EL), Gaithersburg, MD. Energy and Environment Div. 加工时间:2014-08-05 信息来源:科技报告(PB) 索取原文[23 页]
关键词:空气污染;室内空气污染;商业参考建筑;空气质量分析
摘 要:Sixteen commercial reference buildings were created in the multizone airflow and contaminant transport program CONTAM in order to support airflow and indoor air quality (IAQ) analyses, which are not possible using the existing EnergyPlus input files for these buildings. Annual airflow and contaminant simulations were performed in CONTAM for six of the buildings. Contaminant analyses were performed for occupant-generated carbon dioxide (CO2), volatile organic compounds (VOC) from indoor sources, outdoor particulate matter, and outdoor ozone. In all of the selected buildings and zones, the simulated indoor ozone and PM2.5 concentrations did not exceed indoor limits set by the World Health Organization. For CO2 and VOC, for which no similarly relevant indoor concentration standards or limits exist, the simulated concentrations were within expected ranges based on published field measurements in commercial buildings. The results of this study provide a baseline for subsequent use of these models to investigate approaches to building ventilation and other technologies that are intended to simultaneously reduce building energy consumption while maintaining or improving indoor air quality.